APC Dumb UPS cable (simple) pinout |
connector or cable wiring |
APC Part# 940-0020 (grey cable). Should work with APC PowerChute Plus software.
This cable can only be used on voltage-signalling UPSes, and provides the On Battery signal as well as kill UPS power (and may be Low Battery signal).
APC Part# - 940-0020B (investigated by apcupsd team)
Signal Computer UPS
DB9F DB9M
CTS 8 -------------------- 2 On Battery
DTR 4 -------------------- 1 Kill power
GND 5 ---------------*---- 4 Ground
|
--- *---- 9 Common
DCD 1 ----|///|----------- 5 Low Battery
|\\\|
RTS 7 ----|///| (probably a
--- semi-conductor)
Note: sides swapped.
Full scheme of 940-0020C isn't yet known.
APC Part# - 940-0020C (investigated by apcupsd team)
Signal Computer UPS
DB9F DB9M
CTS 8 -------------------- 2 On Battery
DTR 4 -------------------- 1 Kill power
GND 5 ---------------*---- 4 Ground
|
*---- 9 Common
RTS 7 -----[ 93.5K ohm ]----- 5 Low Battery
or semi-conductor
Our users reports that the 20C is designed to mimic a mouse movement when it received an on battery signal from the Back-UPS. Therefore the computer will wake up and shutdown properly. The 20B cable does not have this functionality. | ![]() 9 pin D-SUB female connector | |||||||||||||||||
Pinouts.ru > GPS, UPS, Switches and other devices cables and adapters schematics > Pinout of APC Dumb UPS cable (simple) and layout of 9 pin D-SUB male connector and 9 pin D-SUB female connector |
correct | |
| Source(s) of this and additional information: www.apcupsd.com, UPS FAQ in russian | 7 reports | |