Pin#Signal TypeFunction
1RS-232 Earth GroundSignal Common for all RS-232 port signals (earth ground referenced)
2RS-232 Transmit Output Serial communication mode - output signal line. 
3RS-232 Receive Input / ShutdownSerial communication mode - input signal line. Contact Closure mode - shuts down UPS if signal is held high (RS-232 level) for 200 milliseconds while UPS is operating in battery mode.
4AC Line Fail (normally closed)Contact Closure mode - opened when AC line fails and UPS is operating in battery mode (breaks connection between Pin#4 and Pin#5).
5Contact Closure Common / RS-232  CommonSignal Common for all Contact Closure group / RS-232 Signal Common line.
7Low Battery (normally open)Contact Closure mode - closed when remaining "on-battery runtime" drops below the under-defined time limit (makes connection between Pin#7 and Pin#5).
9AC Line Fail (normally open) Contact Closure mode - closed when in battery mode (makes connection between Pin#9 and Pin#5).


This information should be correct, but may be not. Please, help us to improve this document!
Is this document CORRECT or INCORRECT? Your opinion will be used to establish document status (showed at the bottom).
Pinouts.ru > Some peripheral devices pinouts >  Pinout of HP PowerWise L600/L900/L1250 UPS interface and layout of 9 pin D-SUB male connector
Document status: unknown
0 reports
Last updated at Sat Jun 25 2005. Submit additions or corrections for this document. Is this document correct or incorrect? What is your opinion?
[Discuss at the forum] [Back to index] [SUBMIT new pinout]
This page contain parts under Copyright © 2000-2007 by pinouts.ru team.
No any portion of this webpage may be reproduced in any form without visible direct link to this page provided. Webmaster permission required in any other cases.
Efforts have been made to ensure this page is correct, but it is the responsibility of the user to verify the data is correct for their application.
6874 hits since March 4, 2005