Hardware pinouts information and cables schemes

Liebert UPStation-GXT interface pinout

connector wiring scheme

bookmark this page



Pin#
 
Function
 
1
Low Battery (Optocoupler Collector: +V)
 
2
UPS TxD
 
3
UPS RxD
 
4
Remote ShutDown (+5..12VDC, 10 mA max); on battery operation
 
5
Common
 
6
Remote ShutDown (Short to pin 5); any mode operation
 
7
Low Batery (Optocoupler Emitter: -V)
 
8
Utility/Mains Fail (Optocoupler Emitter: -V)
 
9
Utility/Mains Fail (Optocoupler Collector: +V)

Maximum voltage and current on pins 1,7,8,9 shall be 80 VDC, 10.0 mA max


This information should be correct, but may be not. Please, help us to improve this document!
Is this document CORRECT or INCORRECT? Your opinion will be used to establish document status (showed at the bottom).
Pinouts.ru > Some peripheral devices pinouts >  Pinout of Liebert UPStation-GXT interface and layout of 9 pin D-SUB male connector
Document status: correct
Source(s) of this and additional information: UPS FAQ in russian 1 reports
Last updated at Sat Jun 25 2005. Submit additions or corrections for this document. Is this document correct or incorrect? What is your opinion?
[Discuss at the forum] [Back to index] [SUBMIT new pinout]
This page contain parts under Copyright © 2000-2007 by pinouts.ru team.
No any portion of this webpage may be reproduced in any form without visible direct link to this page provided. Webmaster permission required in any other cases.
Efforts have been made to ensure this page is correct, but it is the responsibility of the user to verify the data is correct for their application.
6580 hits since March 4, 2005